Article Details
Vol. 4 No. 1 (2025): November
Planning the Transfer of a 20 kV Distribution Feeder from Mariana Substation to Tanjung Api-Api Substation for Makarti Jaya Village
Purpose: The rapid population growth and increasing electricity demand in Makarti Jaya Village, Banyuasin Regency, have pushed the Tomato Feeder at Mariana Substation close to its capacity limit. This study designs a medium-voltage feeder transfer by redirecting supply from the near-overloaded Tomato Feeder to the idle Ferry Feeder at Tanjung Api-Api Substation. Methodology: A documentary research approach was used based on technical data from PT PLN (Persero), including feeder loading, substation capacity, and network configuration. Engineering calculations were conducted using SPLN 41-8:1981, AVE D210, and PLN design standards to determine pole requirements, conductor sizing, sag, voltage drop, and voltage regulation.
Results: The proposed 20 kV network requires 642 reinforced concrete poles with AAAC 70 mm² conductors over 96.915 km. The calculated voltage drop is 685.44 V with a voltage regulation of 3.55 percent, remaining within PLN’s ±5 percent standard.
Conclusions: The feeder transfer is technically feasible, reduces system loading, shortens network distance significantly, and maintains acceptable voltage quality.
Limitations: This study focuses only on technical engineering design and does not include economic feasibility analysis, protection coordination, environmental impact assessment, or long-term load growth forecasting.
Contributions: This study provides a structured engineering framework for medium-voltage feeder transfer planning in rural electrification systems, including systematic procedures for pole calculation, conductor selection, sag estimation, and voltage performance evaluation based on PLN standards.

This work is licensed under a Creative Commons Attribution-ShareAlike 4.0 International License.